Dipaké pikeun kontrol jeung aplikasi kakuatan dina tutuwuhan kimia, , tutuwuhan industri, gardu utiliti jeung stasiun generating, wangunan padumukan jeung komérsial.
Dipaké pikeun kontrol jeung aplikasi kakuatan dina tutuwuhan kimia, , tutuwuhan industri, gardu utiliti jeung stasiun generating, wangunan padumukan jeung komérsial.
1. Konduktor: Kelas B terdampar, annealed tambaga bulistir per ASTM B-3 jeung B-8
2. insulasi: Polyvinyl Chloride (PVC), nilon katutupan per UL 83 pikeun Tipe THHN / THWN
3. Kode warna: Konduktor disandi warna per Métode ICEA 4 (nomer dicitak)
4. Majelis: Insulated konduktor anu cabled bareng jeung fillers sakumaha diperlukeun sangkan buleud
5. Gemblengna jaket: Sunlight-tahan Polyvinyl Chloride (PVC) per UL 1277
Spésifikasi Standar ASTM B3 pikeun Kawat Tambaga Lemes atanapi Annealed
ASTM B8 Concentric-Lay-Stranded Tambaga Konduktor
UL 83 Thermoplastic Insulated Kawat jeung Kabel
UL 1277 Daya Listrik sareng Kabel Kontrol Baki
UL 1685 Vertikal-Tray Rambatan Seuneu jeung Haseup Release Test
ICEA S-58-679 Métode Idéntifikasi Konduktor Kabel Kontrol 3 (1-BLACK, 2-RED, 3-BLUE)
ICEA S-95-658 (NEMA WC70) Kabel Daya Dipeunteun 2000 Volt atanapi Kurang pikeun Distribusi Énergi Listrik
Max.rated hawa konduktor: Operasi Nominal 90 ℃.
sirkuit pondok: (Max.for 5 secs) 250 ℃.
Suhu peletakan, dina hawa 25 ℃
Bawah taneuh 15 ℃
Pikeun peletakan, inti tunggal, peletakan segitiga pikeun tilu kabel.
Jero peletakan langsung: 100cm
Koéfisién résistansi termal taneuh 100 ℃.cm/w
Kabel bisa diteundeun tanpa larangan serelek, sarta suhu lingkungan teu kudu leuwih handap 0 ℃.
Inti tunggal, pita baja kabel Armored kedah ngan dilarapkeun ka langsung-circuit garis.
Pikeun ketebalan insulasi nominal, ukuran armor, leuwih-diaméterna, beurat jeung rating ayeuna tina seuneu-retardant
kabel kelas A, B, C, anu kedah ngarujuk kana nilai kabel umum.
Warna sarung: hideung sareng belang beureum
Packing: 500m unggal kendang atawa panjang lianna ogé sadia on pamundut
Nominal Dia.pikeun Tambaga jeung Aluminium konduktor | |||||||
Ukuran konduktor | Padet (mm) | Terdampar | |||||
AWG atanapi KCMIL | mm² | Kompak (mm) | Kelas B Dikomprés | Kelas B | Kelas C | Kelas D | |
18 | 0.823 | 1.02 | 1.17 | ||||
16 | 1.31 | 1.29 | 1.47 | ||||
15 | 1.65 | 1.45 | 1.65 | ||||
14 | 2.08 | 1.63 | 1.79 | 1.84 | 1.87 | 1.87 | |
13 | 2.63 | 1.83 | 2.02 | 2.07 | 2.10 | 2.10 | |
12 | 3.31 | 2.05 | 2.26 | 2.32 | 2.35 | 2.36 | |
11 | 4.17 | 2.30 | 2.53 | 2.62 | 2.64 | 2.64 | |
10 | 5.26 | 2.59 | 2.87 | 2.95 | 2.97 | 2.97 | |
9 | 6.63 | 2.91 | 3.20 | 3.30 | 3.33 | 3.35 | |
8 | 8.37 | 3.26 | 3.40 | 3.58 | 3.71 | 3.76 | 3.76 |
7 | 10.60 | 3.67 | 4.01 | 4.17 | 4.22 | 4.22 | |
6 | 13.30 | 4.11 | 4.29 | 4.52 | 4.67 | 4.72 | 4.72 |
5 | 16.80 | 4.62 | 5.08 | 5.23 | 5.28 | 5.31 | |
4 | 21.10 | 5.19 | 5.41 | 5.72 | 5.89 | 5.94 | 5.97 |
3 | 26.7 | 5.83 | 6.05 | 6.40 | 6.60 | 6.68 | 6.71 |
2 | 33.6 | 6.54 | 6.81 | 7.19 | 7.42 | 7.52 | 7.54 |
1 | 42.4 | 7.35 | 7.59 | 8.18 | 8.43 | 8.46 | 8.46 |
1/0 | 53.5 | 8.25 | 8.53 | 9.17 | 9.45 | 9.50 | 9.50 |
2/0 | 37.4 | 9.27 | 9.55 | 10.30 | 10.60 | 10.70 | 10.70 |
3/0 | 85 | 10.40 | 10.70 | 11.6 | 11.9 | 12.0 | 12.00 |
4/0 | 107 | 11.70 | 12.10 | 13.0 | 13.4 | 13.4 | 13.45 |
250 | 127 | 12.70 | 13.20 | 14.2 | 14.6 | 14.6 | 14.60 |
300 | 152 | 13.90 | 14.50 | 15.5 | 16.0 | 16.0 | 16.00 |
350 | 177 | 15.00 | 15.60 | 16.8 | 17.3 | 17.3 | 17.30 |
400 | 203 | 16.10 | 16.70 | 17.9 | 18.5 | 18.5 | 18.5 |
450 | 228 | 17.00 | 17.80 | 19.0 | 19.6 | 19.6 | 19.6 |
500 | 253 | 18.00 | 18.70 | 20.0 | 20.7 | 20.7 | 20.7 |
550 | 279 | 19.70 | 21.1 | 21.7 | 21.7 | 21.7 | |
600 | 304 | 20.70 | 22.0 | 22.7 | 22.7 | 22.7 | |
650 | 329 | 21.50 | 22.9 | 23.6 | 23.6 | 23.60 | |
700 | 355 | 22.30 | 23.7 | 24.5 | 24.5 | 24.50 | |
750 | 380 | 23.10 | 24.6 | 25.3 | 25.4 | 25.43 | |
800 | 405 | 23.80 | 25.4 | 26.2 | 26.2 | 26.20 | |
900 | 456 | 25.40 | 26.9 | 27.8 | 27.8 | 27.80 | |
1000 | 507 | 26.90 | 28.4 | 29.3 | 29.3 | 29.30 | |
1100 | 557 | 29.8 | 30.7 | 30.7 | 30.78 | ||
1200 | 608 | 31.1 | 32.1 | 32.1 | 32.10 | ||
1250 | 633 | 31.8 | 32.7 | 32.8 | 32.80 | ||
1300 | 659 | 32.4 | 33.4 | 33.4 | 33.40 | ||
1400 | 709 | 33.6 | 34.7 | 34.7 | 34.7 | ||
1500 | 760 | 34.8 | 35.9 | 35.9 | 35.9 | ||
1600 | 811 | 35.9 | 37.1 | 37.1 | 37.1 | ||
1700 | 861 | 37.1 | 38.2 | 38.2 | 38.2 | ||
1750 | 887 | 37.60 | 38.8 | 38.8 | 38.8 | ||
1800 | 912 | 38.2 | 39.3 | 39.3 | 39.3 | ||
1900 | 963 | 39.2 | 40.4 | 40.4 | 40.4 | ||
2000 | 1013 | 40.2 | 41.5 | 41.5 | 41.5 | ||
2500 | 1267 | 44.9 | 46.3 | 46.3 | 46.3 | ||
3000 | 1520 | 49.2 | 50.7 | 50.7 | 50.7 |
Ukuran konduktor, Ketebalan insulasi sareng Tegangan Uji | |||||
Tegangan Sirkuit Dipeunteun (Fase ka Fase) | Ukuran konduktor | Ketebalan insulasi nominal | Tes tegangan AC | Tegangan Tés DC | |
A | B | ||||
V | AWG/ KCMIL | mm | KV | KV | |
0-600 | 43357,00 | 1.016 | 0.762 | 3.5 | 10.5 |
43314.00 | 1.397 | 1.143 | 5.5 | 16.5 | |
1-4/0 | 2.032 | 1.397 | 7 | 21 | |
225-500 | 2.413 | 1.651 | 8 | 24 | |
525-1000 | 2.64 | 2.032 | 10 | 30 | |
1025-2000 | 3.175 | 2.54 | 11.5 | 34 | |
601-2000 | 43357,00 | 1.397 | 1.016 | 5.5 | 16.5 |
43314.00 | 1.778 | 1.397 | 7 | 21 | |
1-4/0 | 2.159 | 1.651 | 8 | 24 | |
225-500 | 2.667 | 1.778 | 9.5 | 28.5 | |
525-1000 | 3.048 | 2.159 | 11.5 | 34.5 | |
1025-2000 | 3.556 | 2.921 | 13.5 | 40 |
Ketebalan Jaket | |||||
Ketebalan jaket pikeun kabel Single-konduktor | Ketebalan umum jaket umum tina kabel sababaraha-konduktor | ||||
Diitung dia.tina kabel handapeun jaket | Ketebalan Jaket | Diitung dia.tina kabel handapeun jaket | Ketebalan Jaket | ||
Min. | Nominal | Min. | Nominal | ||
mm | mm | mm | mm | mm | mm |
6,35 atanapi kirang | 0.33 | 0.38 | 10,8 atanapi kirang | 1.02 | 1.14 |
6.38-10.8 | 0.635 | 0.76 | 10.82-17.78 | 1.27 | 1.52 |
10.82-17.78 | 1.02 | 1.14 | 17.81-38.10 | 1.78 | 2.03 |
17.81-38.1 | 1.4 | 1.65 | 38.13-63.50 | 2.41 | 2.79 |
38.13-63.5 | 2.03 | 2.41 | 63,53 sareng langkung ageung | 3.05 | 3.56 |
63.53 & engké | 2.67 | 3.18 |